Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x In cab emergency telephone does not work and shall be repaired and tested. 1/10/2019
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7 Cab emergency light does not work and shall be repaired. 2/13/2019
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x When 110v is disconnected the in car emergency phone shall work. 10/25/2019
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The emergency phone gives the wrong address when tested and shall be corrected. 10/25/2019
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1001.2(d)(12) - A fire service testing log shall be kept on-site. 10/25/2019
A17.1-1996 : Elevators 3.20 - Governor rope 1001.2(c)(26) x The governor rope shall have a rope data tag. 10/25/2019
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) The in car emergency telephone shall be operational. 12/9/2019
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits The pit light shall work. 12/12/2019
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A maintenance log shall be kept on-site. 12/12/2019
A17.1-1996 : Elevators 2.1 - Access to machine space 1001.2(b)(1) The machine room door shall be self-locking and self-closing. 12/12/2019
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 1001.2(b)(3) Inspection code The machine room lighting shall work. 12/12/2019
A17.1-1996 : Elevators 2.5 - Housekeeping 1001.2(b)(5) The machine room shall be cleaned of dirt and debris. 12/12/2019
A17.1-1996 : Elevators 2.14 - Code data plate 1200.6 A code data plate is required in the machine room. 12/12/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.34 - Flexible Hydraulic Hose and Fitting Assemblies 8.11.3.1.2 (q) The high pressure hose is expired. If the unit is equipped with a rupture valve the hose does not need replacing, if no rupture valve is present the high pressure hose shall be replaced. 2/22/2021
A17.1-2016 : Elevators 5.15.2 Unsealed Overspeed Valve 8.6.5.16.5 (Re-Inspect) x OSV is not sealed. Perform test, tag and seal upon completion. 8/2/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11 Periodic Inspection and Test. x All category 5 testing items are due with the exception of the overspeed valve test. 8/2/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 8/10/2023