Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (H) - Machine Rooms (H)8 No No 4x4 electrical box in machine room needs to have wiring inside box and cover installed 8/12/2026
MO Minimum : Elevators (H) - Machine Rooms (H)8 No No 4x4 electrical box in machine room needs to have wiring inside box and cover installed
A17.1-1996 : Elevators 2.14 - Code data plate 1200.6 No No A code data plate is required in the machine room. 12/12/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 8/10/2023
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1001.2(d)(12) - No No A fire service testing log shall be kept on-site. 10/25/2019
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No A maintenance log shall be kept on-site. 12/12/2019
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7 No No Cab emergency light does not work and shall be repaired. 2/13/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Current State Operating Permit shall be displayed in the Equipment Room in a non-combustible frame. 8/26/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Current State Operating Permit shall be displayed in the Equipment Room in a non-combustible frame. CITED 11/14/2025, NOT COMPLIANT, no Certificate found in machine room. 8/12/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 No No Fire extinguisher is expired. 7/13/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 2.7.5.1 Lighting No No Machine room lighting needs to be repaired, 1 or more bulbs not working. 8/12/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 2.7.5.1 Lighting No No Machine room lighting needs to be repaired, 1 or more bulbs not working.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 No No Machine Room shall have proper Fire Extinguisher and shall have current monthly/annual test tag
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 No No Machine Room shall have proper Fire Extinguisher and shall have current monthly/annual test tag 8/12/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.6 - Ventilation 2.7.5.2 No No Machine room ventilation fan shall work. Thermostat appears stuck. 8/12/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.6 - Ventilation 2.7.5.2 No No Machine room ventilation fan shall work. Thermostat appears stuck.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.11 - Disconnecting Means and Control 2.26.4 No No Mainline disconnect is severely water damaged.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.11 - Disconnecting Means and Control 2.26.4 No No Mainline disconnect is severely water damaged. 8/12/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No No MO State operating certificate in the machince room. 7/13/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits No No Pit shall be kept dry. Remove rust from pit equipment , repair/replace as needed, apply rust prevention treatment to all pit steel, investigate/repair water leak 8/12/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits No No Pit shall be kept dry. Remove rust from pit equipment , repair/replace as needed, apply rust prevention treatment to all pit steel, investigate/repair water leak
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.1 - Top-of-car stop switch 2.26.2.8 No No Stop switch on top of car is broken. 7/13/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.34 - Flexible Hydraulic Hose and Fitting Assemblies 8.11.3.1.2 (q) No No The high pressure hose is expired. If the unit is equipped with a rupture valve the hose does not need replacing, if no rupture valve is present the high pressure hose shall be replaced. 2/22/2021
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) No No The in car emergency telephone shall be operational. 12/9/2019
A17.1-1996 : Elevators 2.1 - Access to machine space 1001.2(b)(1) No No The machine room door shall be self-locking and self-closing. 12/12/2019
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 1001.2(b)(3) Inspection code No No The machine room lighting shall work. 12/12/2019
A17.1-1996 : Elevators 2.5 - Housekeeping 1001.2(b)(5) No No The machine room shall be cleaned of dirt and debris. 12/12/2019
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits No No The pit light shall work. 12/12/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.12 - Car enclosure 2.14 No No Tighten/repair car interior handrail. 8/12/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.12 - Car enclosure 2.14 No No Tighten/repair car interior handrail.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Emergency Lighting Yes No ) EMERGENCY LIGHTING SHALL WORK WITH LOSS OF MAIN 120v POWER 8/12/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes Yes 2-WAY COMMUNICATION DEVICE SHALL WORK. 8/12/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11 Periodic Inspection and Test. Yes No All category 5 testing items are due with the exception of the overspeed valve test. 8/2/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Emergency Lighting Yes No EMERGENCY LIGHTING SHALL WORK WITH LOSS OF MAIN 120v POWER
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency phone shall be operational. Dials out but no answer. 7/13/2026
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No In cab emergency telephone does not work and shall be repaired and tested. 1/10/2019
A17.1-2016 : Elevators 5.15.2 Unsealed Overspeed Valve 8.6.5.16.5 (Re-Inspect) Yes No OSV is not sealed. Perform test, tag and seal upon completion. 8/2/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing Yes No OSV shall have current testing tag. 5yr weight test last performed 4/9/2021 8/12/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing Yes No OSV shall have current testing tag. 5yr weight test last performed 4/9/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.7 Firefighters' Emergency Operation: Operating Procedures Yes Yes Phase I fire service return there, is no buzzer(not working). 8/12/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.7 Firefighters' Emergency Operation: Operating Procedures Yes No Phase I fire service return there, is no buzzer. 7/13/2026
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No The emergency phone gives the wrong address when tested and shall be corrected. 10/25/2019
A17.1-1996 : Elevators 3.20 - Governor rope 1001.2(c)(26) Yes No The governor rope shall have a rope data tag. 10/25/2019
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No When 110v is disconnected the in car emergency phone shall work. 10/25/2019