ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection)
|
x
|
|
1.18.1: Car Door restrictor shall work. (REINSPECTION WITHIN 30 DAYS)
|
9/10/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
2-way communication device shall work and give proper location. (REINSPECTION within 30 days)
|
9/10/2020
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
2021&2022 I(1)/106.1 Pit shall be kept clean and free of excessive debris. (Reported as compliant on 4/27/22, ) NOT compliant as of this inspection.
|
11/16/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
8.6.1.6.5 Machine Room Fire Extinguisher has been removed from room, replace
|
11/16/2022
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
B(11)/1.6.1/ : 2-way communication device shall work (REINSPECTION 14days to REDTAG)
|
10/24/2022
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
B(11)/1.6.1/ : 2-way communication device shall work (REINSPECTION 14days to REDTAG)
|
10/24/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
Compliant/Required Documentation & MCP shall be kept in equipment room(neat/organized) including Wiring Diagrams, Oil log &Fire service log, recorded monthly. (Provided by Elev Co.)
|
11/16/2022
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Current State Operating Permit shall be displayed in the Equipment Room in a non-combustible frame. (Cert on display expired 2019)
|
11/16/2022
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Must make Emergency phone operable. 1.6
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit shall be kept clean and free of excessive debris.
|
4/27/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
telephone will not call out
|
7/29/2018
|