Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Emergency power operation shall be tested.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Current State operating certificate must be displayed in the machine room.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) A code compliant MCP with related on-site documentation shall be located in the machine room.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Machine room shall have proper fire extinguisher and shall have current monthly/annual test tag.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.11.1 Firefighters' Emergency Operation & Documentation Fire service testing must be documented monthly.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate x A state ID sticker shall be posted on the elevator controller. 7/17/2023
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 8.10.2.2.3(r) x There is coax and other cables running the length of the hoistway shall be removed from the hoistway. Only pipes, wiring, and ducts used in connection with the elevator may be installed in the hoistway, remove the cables. 7/17/2023
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2 On-Site Documentation x A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 7/17/2023
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2(b)(1) x Need procedures for inspections and tests not described in A17.2. 7/17/2023
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2(d)(1) x Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. 7/17/2023
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits The pit shall be kept clean. Remove excess debris. 3/11/2026