ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
9/15/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2 Design and Construction of Pits
|
|
|
The pit equipment and oil lines are excessively rusted. Rust and corrosion shall be removed and equipment shall be painted with a rust proof paint.
|
7/24/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2.6 Sump Pump Covers
|
|
|
A sump pump cover is required in the pit.
|
9/15/2021
|
conversion
|
conversion
|
n/a
|
|
|
Hydraulic line, buffers, and pit equipment are excessively rusty. The pit equipment shall have corrosion removed and a rust inhibitor applied.
|
7/24/2019
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Existing cab emergency telephone doe not work and shall be repaired and tested.
|