Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Elevator pit must be kept free of Debris. 8.6.4.7 1/24/2023
A17.1-1996 : Elevators 1.1 - Door Re-opening device 1001.2(a)(1) Rear Gate Re-opening devise must be made operable. 1001.2(a)(1) 1/24/2023
A17.1-1996 : Elevators 1.1 - Door Re-opening device 1001.2(a)(1) Must repair or replace Protective Boot for gate re-opening device front gate. 1001.2(a)(1). (cuts tears and missing section) 1/24/2023
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.7 Firefighter' Service Operating Procedures Must make Phase II fire service operable. 211.7 ( doors operate properly but car will not leave primary floor) 1/24/2023
A17.1-1996 : Elevators 1.1 - Door Re-opening device 1001.2(a)(1) Both front and rear gate reopening devises need replaced 2/7/2020
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 211.8 Switch Keys Must make Phase II Fire Service Key Switch Operable. 6.4
A17.1-2016 : Elevators 5.15 - Overspeed Valve 8.6.5.16.5 Must perform Cat 5 OSV (over speed valve)test/insp.
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) x Must make Emergency light operable. 1.5 1/9/2023
A17.1-1996 : Elevators 1.6 - Car emergency signal 1004.2(a)(6) (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Must make Emergency alarm operable. 1.6 1/9/2023
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Must Make Emergency Alarm Operable. 8.6.4.15