Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits 8.6.4.7.3 - Pit machine space door shall be self-closing and self-locking and shall be left in the closed position. 8/22/2023
MO Minimum : Elevators (H) - Machine Rooms (H)2 Water is entering the machine room from the ceiling near motor generator. Correct the source of the leak. 11/15/2019
MO Minimum : Elevators (H) - Machine Rooms (H)2 Windows in the machine room are damaged or missing, repair or replace as needed. 11/15/2019
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting In car emergency lights shall work. 11/15/2019
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x In car emergency bell shall work. 11/15/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x The in car emergency telephone shall be operational. 2/16/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 8/22/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods Correct cause of door clutch hitting hoistway door pickup rollers. 8/22/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x A sprinkler system is being added to the machine room which will require the installation of a code compliant shunt trip disconnect. 8/18/2022
MO Minimum : Elevators (I) - Pits (I)1 The pit shall be kept clean. Remove oil and water from pit floor. 8/22/2023
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room needs to be cleaned out. 8/22/2023
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Once the doors open completely while on Phase 2 operation, they shall remain open. 3/29/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency bell shall be operational on battery backup. 3/29/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency light shall be operational on battery backup. 3/29/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.7 Cleaning of Hoistway and Pit Hoistway is in need of a clean down. 8/22/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) A written Maintenance Control Program (MCP) shall be in place to maintain the equipment in compliance with the requirements of Section A17.1 - 2016 - 8.6. MCP is missing Evacuation procedures. 8/22/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x A sprinkler system is being added to the machine room which will require the installation of a code compliant shunt trip disconnect. (Uncleared violation from 2021). 3/29/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Some of the stairwells have been blocked off as some upper floors are not being used. The machine room for the elevators are located above the areas that are blocked off. The stairwells shall be cleared to allow egress in case of an emergency or fire. This is a life safety issue. 3/29/2023
MO Minimum : Elevators (M) - Car Safeties and Speed Governors (M)4 x x The safety drum rope shall not pullout more than 36". Currently pulls out 57". Elevator Red-Tagged. 4/3/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) MCP is missing evacuation procedures. 8/22/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams No prints in the machine room. 8/22/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency light/bell shall be operational on main power and battery back up. (Uncleared prior inspection violation) 4/3/2023
MO Minimum : Elevators (I) - Pits (I)1 x The pit shall be kept clean. Remove oil and water from pit floor. (Uncleared prior inspection violation) 4/3/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces x Machine room needs to be cleaned out. (Uncleared prior inspection violation) 4/3/2023
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Once the doors open completely while on Phase 2 operation, they shall remain open. (Uncleared prior inspection violation) 4/3/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.7 Cleaning of Hoistway and Pit x Hoistway is in need of a clean down. (Uncleared prior inspection violation) 4/3/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x A sprinkler system is being added to the machine room which will require the installation of a code compliant shunt trip disconnect. (Uncleared violation from 2021). 4/3/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Some of the stairwells have been blocked off as some upper floors are not being used. The machine room for the elevators are located above the areas that are blocked off. The stairwells shall be cleared to allow egress in case of an emergency or fire. This is a life safety issue. (Uncleared prior inspection violation) 4/3/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Elevator is due for a category 5 test. 4/3/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency light/bell shall be operational on main power and battery back up. (Uncleared prior inspection violation) 5/17/2023
MO Minimum : Elevators (I) - Pits (I)1 x The pit shall be kept clean. Remove oil and water from pit floor. (Uncleared prior inspection violation) 5/17/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces x Machine room needs to be cleaned out. (Uncleared prior inspection violation) 5/17/2023
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Once the doors open completely while on Phase 2 operation, they shall remain open. (Uncleared prior inspection violation) 5/17/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.7 Cleaning of Hoistway and Pit x Hoistway is in need of a clean down. (Uncleared prior inspection violation) 5/17/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x A sprinkler system is being added to the machine room which will require the installation of a code compliant shunt trip disconnect. (Uncleared violation from 2021). 5/17/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Some of the stairwells have been blocked off as some upper floors are not being used. The machine room for the elevators are located above the areas that are blocked off. The stairwells shall be cleared to allow egress in case of an emergency or fire. This is a life safety issue. (Uncleared prior inspection violation) 5/17/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Elevator is due for a category 5 test. 5/17/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Replace extra fire service phase 1 key switch that has been disconnected at the 1st floor with a blank cover. 8/22/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Replace the missing up-thrust at the 2nd floor. 8/22/2023