Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements 8.6.1.6.3(b) clean control cabnets 8/14/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x 8.6.4.15 emergency light needs battery 8/8/2019
MO Minimum : Elevators (H) - Machine Rooms (H)4 clean machine room floor of all oil and greese 8/14/2019
MO Minimum : Elevators (S) - Fire Service (S)1 x Phase I key switch needs replaced 6/13/2019
A17.1-2016 : Elevators 1.18 - Restricted opening of car or hoistway doors 8.6.4.19.16 x Must Make car door restrictor operable. 1.18 11/15/2024
A17.1-2016 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 2.4.2 x Must Maintain Min. 6" counterweight Runby. (currently 5") 2.4.2 11/15/2024