conversion
|
conversion
|
n/a
|
|
|
truss , upper & lower end need clean down
|
6/24/2019
|
conversion
|
conversion
|
n/a
|
|
|
Upper and lower lights & guasrds in truss need replaced
|
6/24/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators
|
7.5 - Lighting
|
8.6.11.5(i) Demarcation Lighting (Re-Inspect)
|
x
|
|
2019-2020: Step demarcation lights not working upper and lower (2nd year violation)
|
12/24/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators
|
8.1 - Machinery space access, lighting, receptacle, and condition
|
6.1.7
|
|
|
Escalator machine spaces(pits) lighting and receptacles will not be controlled by facility “lighting timers”.
|
12/24/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators
|
8.1 - Machinery space access, lighting, receptacle, and condition
|
8.6.8.13
|
|
|
Escalator machine spaces(pits) shall be kept clean and free from excessive debris.
|
12/24/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators
|
8.1 - Machinery space access, lighting, receptacle, and condition
|
8.6.8.13
|
|
|
2018&2020: Truss , upper & lower end need clean down (violation not corrected as of 8/2020)
|
12/24/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators
|
7.9 - Steps and upthrust device
|
6.1.3.5.6
|
|
|
:Replace broken step demarcation sections. Reinspection within 30 days
|
12/24/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators
|
7.9 - Steps and upthrust device
|
8.6.8.6
|
x
|
|
Slotting in step treads will be parallel with direction of travel. Repair or replace step with bent tread section. (REINSPECTION WITHIN 30 DAYS)
|
12/24/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators
|
7.9 - Steps and upthrust device
|
8.6.8.6
|
x
|
|
Slotting in step treads will be parallel with direction of travel. Repair or replace step with bent tread section. (REINSPECTION WITHIN 30 DAYS)
|
9/1/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Certificate
|
|
|
needs current certificate posted
|
1/14/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators
|
7.9 - Steps and upthrust device
|
8.6.8.6
|
x
|
|
Replace broken step Demarcation sections
|
1/14/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators
|
8.1 - Machinery space access, lighting, receptacle, and condition
|
6.1.7
|
|
|
Escalator machine spaces(pits) lighting and receptacles will not be controlled by facility “lighting timers”.
|
1/14/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators
|
8.1 - Machinery space access, lighting, receptacle, and condition
|
8.6.8.13
|
|
|
Escalator machine spaces(pits) shall be kept clean and free from excessive debris.
|
1/14/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators
|
8.1 - Machinery space access, lighting, receptacle, and condition
|
8.6.8.13
|
|
|
2018&2020: Truss , upper & lower end need clean down (violation not corrected as of 8/2020)
|
1/14/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators
|
7.9 - Steps and upthrust device
|
6.1.3.5.6
|
|
|
:Replace broken step demarcation sections. Reinspection within 30 days
|
1/14/2022
|
A17.1-2016 : Elevators
|
7.9 - Steps and upthrust device
|
8.6.8.6
|
|
|
Slotting in step treads will be parallel with direction of travel. Repair or replace step with bent tread section. (REINSPECTION WITHIN 30 DAYS)
|
1/14/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators
|
7.3 - Handrails
|
6.1.3.4 (Hand rails) (Re-Inspection)
|
x
|
|
/7.3.1(a) Handrails will be free of major cracks and pinchpoints. Replace both Handrails. REINSPECTION REQUIRED
|
11/21/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators
|
7.9 - Steps and upthrust device
|
6.1.3.5.6
|
x
|
|
Replace loose/damaged/broken step demarcation sections. REINSPECTION REQUIRED
|
11/21/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators
|
8.1 - Machinery space access, lighting, receptacle, and condition
|
8.11.4.2.1 (Re-Inspection)
|
x
|
|
8.1.2: Escalator machine spaces(upper and lower pits) shall be kept clean and free from excessive debris. MULTI-YEAR VIOLATION=
|
11/21/2022
|
Missouri Minimum : Escalators
|
(T) - Existing Dumbwaiters, Escalators and Moving Walks
|
8.6.8.13 Escalator Cleaning
|
|
|
Perform annual clean down
|
12/1/2023
|
A17.1-2016 : Elevators
|
8.12 - Steps, step chains, and trusses
|
8.6.8.13
|
|
|
Preform annual clean down
|
8/9/2024
|