Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x ALARM BELL SHALL WORK WITH LOSS OF MAIN 120v POWER (REINSPECTION => 30days) (broken button) 10/31/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting Lamps(overhead Cab lighting) shall be guarded. Missing ceiling panels. 11/22/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Machine Room Fire Extinguisher shall have current monthly/annual test tag, no date present. (4lb ABC, replace with appropriate) 11/22/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers G/2.7.1/8.6.1.6.5: Machine Room Fire Extinguisher shall have current monthly/annual test tag. No tag 9/23/2021
MO Minimum : Elevators (H) - Machine Rooms (H)8 Permanently mount telephone line/flex to wall per NEC code 9/23/2021
MO Minimum : Elevators (I) - Pits (I)1 Repair sump pump, spraying pit equipment, clean pit, remove rust from piping/jack. Repaint to reduce future rusting. Monitor for leaks. 11/22/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.18 - Restricted opening of car or hoistway doors 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) x 1.18.1: Car Door restrictor shall work. (REINSPECTION WITHIN 30 DAYS) 1/22/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.18 - Restricted opening of car or hoistway doors 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) x 1.18.1: Car Door restrictor shall work. (REINSPECTION WITHIN 30 DAYS) 1/22/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.3 Guards Between Adjacent Pits Pit shall be kept dry. Remove rust from pit channels, repaint, repair water leak. 1/22/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.3 Guards Between Adjacent Pits Pit shall be kept dry. Remove rust from pit channels, repaint, repair water leak. 1/25/2021