Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (H) - Machine Rooms (H)2 H(2) / 101.3d(1)(b) Machine room door shall be self-closing and self-locking 3/14/2023
MO Minimum : Elevators (I) - Pits (I)5 I(5). : Pit Ladder shall be installed , accessible from each Pit access opening for each elevator. 3/14/2023
A17.2-2014 : Elevators 1.6 - Car emergency signal 1.6.1 x telephone calls out but then disconnects phone line 1/8/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.23 - Suspension rope 2.20 3.23/2.20.9.8 : Suspension rope shackles while have “anti-rotation”device installed. 3/14/2023
A17.2-2014 : Elevators 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection 2.43.1 rope gripper needs repaired and put back back in operation & tested withen 30 days or RED tagged 1/7/2019
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Up date certificate 1/30/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Provide proper maintenance Records 1/30/2023
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Must make Emergency Phone operable. 8.6.4.15