MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
The signage for “In Case of Fire Use Stairs” is missing from a number of landings. Install signage that conforms to the building code this elevator was installed to meet.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
The signage for “In Case of Fire Use Stairs” is missing from a number of landings. Install signage that conforms to the building code this elevator was installed to meet.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
The signage for “In Case of Fire Use Stairs” is missing from a number of landings. Install signage that conforms to the building code this elevator was installed to meet.
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
The testing has not been completed on the elevator at this time. The backup emergency power and fireman’s service shall be tested before the inspection is completed.
|
8/16/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.13 - Governor,overspeed switch and seal
|
8.11.2.1.2(bb)
|
x
|
x
|
Upon performing the required annual test, the elevator safety governor was found to be degraded to a degree that the activation would not set. Repair or replacement of the governor is required and a reinspection shall be performed before the elevator can be returned to service.
|
8/14/2020
|