Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.13 - Governor,overspeed switch and seal 8.11.2.3.2 x x An excessive amount of wear was found on the governor sheave and would not allow the elevator car safeties to activate as designed. The governor shall be replaced before the elevator will be allowed to return to service. A reinspection and alteration permit is required. 9/7/2018
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The testing has not been completed on the elevator at this time. The backup emergency power and fireman’s service shall be tested before the inspection is completed. 8/16/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The testing has not been completed on the elevator at this time, only emergency power and fire service testing has been completed. The weight test shall be performed, safeties set, governor tested, and buffers compressed before the inspection is completed. 9/6/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates The signage for “In Case of Fire Use Stairs” is missing from a number of landings. Install signage that conforms to the building code this elevator was installed to meet.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates The signage for “In Case of Fire Use Stairs” is not located on all landings.. Install signage that conforms to the building code this elevator was installed to meet.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates The signage for “In Case of Fire Use Stairs” is missing from a number of landings. Install signage that conforms to the building code this elevator was installed to meet.