Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No emergency phone did not connect to answering service 11/14/2023
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year. 7/18/2025
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy annually. the certificate in the machine room is from 2017 7/18/2025
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.11.2.1.2(j) No No Machine room fire extinguisher inspection tag is more than a year old, it is to be inspected and tagged annually. 7/18/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.19 - Guide rails fastening and equipment 8.11.2.1.3(y) No No replace bad roller guides on the bottom of the car (8.6.2.1) 7/28/2025
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) No No A Maintenance Control Program (MCP) for each unit shall be provided by the person and/or firm maintaining the equipment and shall be viewable onsite by elevator personnel at all times. 7/18/2025
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(c) No No The Maintenance Control Program On-Site documents are not in the machine room. 7/18/2025
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(a)(1) No No Did not have a written record of the maintenance performed on this elevator in the machine room. 7/18/2025
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(c)(2) No No A record of findings for firefighters’ service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept in the machine room. 7/18/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.2 - Hoistway doors 8.6.4.13 No No replace bad hoistway door roller on the fast door on the bottom landing (8.6.2.1) 7/28/2025
conversion conversion conversion - reinspect Yes No Repair brake system, did not lower and hold at floor level 125% load 5/7/2019
conversion conversion n/a No No repair top of hoistway machine space work light it did not work 5/13/2020
conversion conversion n/a No No repair governor remote trip/reset device it did not work 5/13/2020