Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(c) The Maintenance Control Program On-Site documents are not in the machine room.
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The emergency lights did not come on, the alarm bell worked, replace the batteries, verify the battery charger is functioning. 6/3/2022
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 8.11.2.1.2(f) light in the alcove for the machine space is burnt out, when it did work it did not provide the required illumination at the floor of 19 foot candles
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year.
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy annually. the one in the machine room is from 2017
A17.1-2016 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Car Emergency System (Re-Inspection) x Emergency lights did not come on, repair emergency light system. 5/23/2023
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) A Maintenance Control Program (MCP) for each unit shall be provided by the person and/or firm maintaining the equipment and shall be viewable onsite by elevator personnel at all times.
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(c)(2) A record of findings for firefighters’ service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept in the machine room.
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(a)(1) Did not have a written record of the maintenance performed on this elevator in the machine room.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 2.7.5.1 needs additional light fixture over the governor and machine, illumination not up to code standard of 19 foot candles measured at the floor
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 8.11.2.1.2(c) the alcove for the machine and the governor does not have adequate illumination, shall be not less than 200 lux (19 foot-candles) at the floor level. Measured around 3 foot-candles
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.8 - Door closing force 8.11.2.1.1(h) x adjust the door closing force to below 30lbf, measured over 35lbf 5/14/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.5 - Access to Hoistway 8.6.4.14 Hoistway Access Switches repair hoistway access keyswitch on the bottom landing, it is pushed into the jamb and not usable
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 8.11.2.1.2(c) the alcove for the machine and governor does not ave adequate illumination of 19 foot candles at the floor
conversion conversion n/a Repair hoistway access keyswitch in the bottom landing jamb
conversion conversion n/a Repair the emergency light system the lights did not come on