Repair hoistway access keyswitch in the bottom landing jamb
|
|
conversion
|
conversion
|
n/a
|
|
|
Repair the emergency light system the lights did not come on
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.3 - Lighting and receptacles
|
8.11.2.1.2(c)
|
|
|
the alcove for the machine and the governor does not have adequate illumination, shall be not less than 200 lux (19 foot-candles) at the floor level. Measured around 3 foot-candles
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
4.5 - Access to Hoistway
|
8.6.4.14 Hoistway Access Switches
|
|
|
repair hoistway access keyswitch on the bottom landing, it is pushed into the jamb and not usable
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.3 - Lighting and receptacles
|
8.11.2.1.2(c)
|
|
|
the alcove for the machine and governor does not ave adequate illumination of 19 foot candles at the floor
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(c)
|
|
|
The Maintenance Control Program On-Site documents are not in the machine room.
|
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
8.11.2.1.2(f)
|
|
|
light in the alcove for the machine space is burnt out, when it did work it did not provide the required illumination at the floor of 19 foot candles
|
|
A17.1-2016 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year.
|
|
A17.1-2016 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy annually. the one in the machine room is from 2017
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.3 - Lighting and receptacles
|
2.7.5.1
|
|
|
needs additional light fixture over the governor and machine, illumination not up to code standard of 19 foot candles measured at the floor
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(a)
|
|
|
A Maintenance Control Program (MCP) for each unit shall be provided by the person and/or firm maintaining the equipment and shall be viewable onsite by elevator personnel at all times.
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4.1(c)(2)
|
|
|
A record of findings for firefighters’ service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept in the machine room.
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4.1(a)(1)
|
|
|
Did not have a written record of the maintenance performed on this elevator in the machine room.
|
|
A17.1-2016 : Elevators
|
1.5 - Car lighting and receptacles
|
8.6.4.15 Car Emergency System (Re-Inspection)
|
x
|
|
Emergency lights did not come on, repair emergency light system.
|
5/23/2023
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The emergency lights did not come on, the alarm bell worked, replace the batteries, verify the battery charger is functioning.
|
6/3/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.8 - Door closing force
|
8.11.2.1.1(h)
|
x
|
|
adjust the door closing force to below 30lbf, measured over 35lbf
|
5/14/2020
|