Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No The emergency lights did not come on, the alarm bell worked, replace the batteries, verify the battery charger is functioning. 6/6/2022
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(c) No No The Maintenance Control Program On-Site documents are not in the machine room. 7/28/2025
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year. 7/28/2025
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy annually. 7/28/2025
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) No No A Maintenance Control Program (MCP) for each unit shall be provided by the person and/or firm maintaining the equipment and shall be viewable onsite by elevator personnel at all times. 7/28/2025
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(c)(2) No No A record of findings for firefighters’ service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept in the machine room. 7/28/2025
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(a)(1) No No Did not have a written record of the maintenance performed on this elevator in the machine room. 7/28/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No Provide updated maintenance task log for 2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Emergency Lighting Yes No Repair emergency cab lighting
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.28 - Counterweight and counterweight buffer 8.11.2.1.3(m) No No Provide proper counterweight runby - shorten hoist ropes
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.18 - Restricted opening of car or hoistway doors 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) Yes No Install car door restrictor brackets on long fascia runs in hoistway
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.2 (Re-Inspection) Yes No Install electrical box cover next to pit ladder - NEC code
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 Illumination of Pits No No Repair/replace pit lighting
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.9 - Floor and emergency identification numbering 8.11.2.1.3(o) No No the top two floor are numbered 7 and 8 on the hoistway side while the jambs are numbered 8 and 9. change the hoistway number to match the jamb number to avioid confusion 7/28/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.5 - Access to Hoistway 8.11.2.1.4(e) No No repair top landing hoistway access keyswitch, it would not run the elevator in the down direction 7/28/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.8 - Door closing force 8.11.2.1.1(h) Yes No adjust the door close to below 30lbf, measured over 35lbf 5/15/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.9 - Floor and emergency identification numbering 8.11.2.1.3(o) No No the top two landing the hoistway side numbers do not match the jamb numbers, renumber the hoistway side to match the jamb numbers 7/28/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.5 - Access to Hoistway 8.6.4.14 Hoistway Access Switches No No repair the top landing hoistway access, could not run the elevator down 7/28/2025
conversion conversion n/a No No hoistway door identification numbering on the top two landings does not match the jamb braille, redo the door numbering to match the jamb braille 7/28/2025