Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.8 - Door closing force 8.11.2.1.1(h) x adjust the door close to below 30lbf, measured over 35lbf 5/15/2020
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The emergency lights did not come on, the alarm bell worked, replace the batteries, verify the battery charger is functioning. 6/6/2022
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(c) The Maintenance Control Program On-Site documents are not in the machine room. 7/28/2025
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year. 7/28/2025
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy annually. 7/28/2025
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) A Maintenance Control Program (MCP) for each unit shall be provided by the person and/or firm maintaining the equipment and shall be viewable onsite by elevator personnel at all times. 7/28/2025
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(c)(2) A record of findings for firefighters’ service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept in the machine room. 7/28/2025
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(a)(1) Did not have a written record of the maintenance performed on this elevator in the machine room. 7/28/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.9 - Floor and emergency identification numbering 8.11.2.1.3(o) the top two landing the hoistway side numbers do not match the jamb numbers, renumber the hoistway side to match the jamb numbers 7/28/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.5 - Access to Hoistway 8.6.4.14 Hoistway Access Switches repair the top landing hoistway access, could not run the elevator down 7/28/2025
conversion conversion n/a hoistway door identification numbering on the top two landings does not match the jamb braille, redo the door numbering to match the jamb braille 7/28/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.9 - Floor and emergency identification numbering 8.11.2.1.3(o) the top two floor are numbered 7 and 8 on the hoistway side while the jambs are numbered 8 and 9. change the hoistway number to match the jamb number to avioid confusion 7/28/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.5 - Access to Hoistway 8.11.2.1.4(e) repair top landing hoistway access keyswitch, it would not run the elevator in the down direction 7/28/2025