Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year. 7/28/2025
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy annually. 7/28/2025
conversion conversion n/a hoistway side of the top two landing doors are not numbered the same as the jamb braille, redo floor indentifaction numbering to match the jamb braille 7/28/2025
conversion conversion n/a repair the top of car inspection controls, the up direction did not work 7/28/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.9 - Floor and emergency identification numbering 8.11.2.1.3(o) the top two landing are numbered 7 and 8 on the hoistway side while the jambs are numbered 8 and 9. Change the hoistway side numbers to match the jamb numbers to eliminate confusion 7/28/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.9 - Floor and emergency identification numbering 8.11.2.1.3(o) the top two landing the hoistway side door number are not the same as the jamb braille numbers, renumber the hoistway side to match the jamb numbers 7/28/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.3 - Top-of-car operating device 8.11.2.1.3(c) repair the car top inspection station, it will not run the elevator up 7/28/2025
A17.1-2016 : Elevators 2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection 2.19.2 rope gripper has a bad leak, repair or replace rope gripper 7/28/2025
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(c) The Maintenance Control Program On-Site documents are not in the machine room. 7/28/2025
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) A Maintenance Control Program (MCP) for each unit shall be provided by the person and/or firm maintaining the equipment and shall be viewable onsite by elevator personnel at all times. 7/28/2025
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(c)(2) A record of findings for firefighters’ service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept in the machine room. 7/28/2025
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(a)(1) Did not have a written record of the maintenance performed on this elevator in the machine room. 7/28/2025