conversion
|
conversion
|
n/a
|
No
|
No
|
hoistway side of the top two landing doors are not numbered the same as the jamb braille, redo floor indentifaction numbering to match the jamb braille
|
7/28/2025
|
|
conversion
|
conversion
|
n/a
|
No
|
No
|
repair the top of car inspection controls, the up direction did not work
|
7/28/2025
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.9 - Floor and emergency identification numbering
|
8.11.2.1.3(o)
|
No
|
No
|
the top two landing are numbered 7 and 8 on the hoistway side while the jambs are numbered 8 and 9. Change the hoistway side numbers to match the jamb numbers to eliminate confusion
|
7/28/2025
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.3 - Top-of-car operating device
|
8.11.2.1.3(c)
|
No
|
No
|
repair the car top inspection station, it will not run the elevator up
|
7/28/2025
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.9 - Floor and emergency identification numbering
|
8.11.2.1.3(o)
|
No
|
No
|
the top two landing the hoistway side door number are not the same as the jamb braille numbers, renumber the hoistway side to match the jamb numbers
|
7/28/2025
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(c)
|
No
|
No
|
The Maintenance Control Program On-Site documents are not in the machine room.
|
7/28/2025
|
|
A17.1-2016 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year.
|
7/28/2025
|
|
A17.1-2016 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy annually.
|
7/28/2025
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(a)
|
No
|
No
|
A Maintenance Control Program (MCP) for each unit shall be provided by the person and/or firm maintaining the equipment and shall be viewable onsite by elevator personnel at all times.
|
7/28/2025
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4.1(c)(2)
|
No
|
No
|
A record of findings for firefighters’ service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept in the machine room.
|
7/28/2025
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.4.1(a)(1)
|
No
|
No
|
Did not have a written record of the maintenance performed on this elevator in the machine room.
|
7/28/2025
|
|
A17.1-2016 : Elevators
|
2.43 - Emergency Brake, Ascending Car Overspeed, and Unintended Car Movement Protection
|
2.19.2
|
No
|
No
|
rope gripper has a bad leak, repair or replace rope gripper
|
7/28/2025
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
No
|
No
|
Provide updated maintenance task log for 2026
|
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
8.6.4.15 Emergency Lighting
|
Yes
|
No
|
Repair emergency cab lighting
|
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection)
|
Yes
|
No
|
Install car door restrictor angles on long fascia runs in hoistway
|
|