Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.8 Switch Keys the phase one key that operated the phase one keyswitch was different from the key used to operate the phase 2 keyswitch
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy annually. could not find a copy of the state certificate in the machine room
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year.
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The emergency lights did not come on, the alarm bell didn't work either, replace the batteries, verify the battery charger is functioning. 6/9/2022
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.11.2.1.2(j) Machine room fire extinguisher inspection tag is from 2019, it is to be inspected and tagged annually.
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) A Maintenance Control Program (MCP) for each unit shall be provided by the person and/or firm maintaining the equipment and shall be viewable onsite by elevator personnel at all times.
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(c) The Maintenance Control Program On-Site documents are not in the machine room.
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(a)(1) Did not have a written record of the maintenance performed on this elevator in the machine room.
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(c)(2) A record of findings for firefighters’ service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept in the machine room.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x emergency phone continues to ring even after answering service answers the phone, the ringing makes two way conversation next to impossible 11/14/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.7 - Car door or gate 8.11.2.1.1(g) replace the car gate astragal, it is torn in several places - 8.6.4.13.1(g)
conversion conversion n/a emergency phone did not work, phone line tested good, repair/replace the phone 5/12/2020