Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a emergency phone did not work, phone line tested good, repair/replace the phone 5/12/2020
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year.
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(c) The Maintenance Control Program On-Site documents are not in the machine room.
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.11.2.1.2(j) Machine room fire extinguisher inspection tag is from 2019, it is to be inspected and tagged annually.
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.8 Switch Keys the phase one key that operated the phase one keyswitch was different from the key used to operate the phase 2 keyswitch
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy annually. could not find a copy of the state certificate in the machine room
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) A Maintenance Control Program (MCP) for each unit shall be provided by the person and/or firm maintaining the equipment and shall be viewable onsite by elevator personnel at all times.
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(c)(2) A record of findings for firefighters’ service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept in the machine room.
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(a)(1) Did not have a written record of the maintenance performed on this elevator in the machine room.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.7 - Car door or gate 8.11.2.1.1(g) replace the car gate astragal, it is torn in several places - 8.6.4.13.1(g)
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x emergency phone continues to ring even after answering service answers the phone, the ringing makes two way conversation next to impossible 11/14/2023
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The emergency lights did not come on, the alarm bell didn't work either, replace the batteries, verify the battery charger is functioning. 6/9/2022