ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
8.11.2.1.5(b)
|
x
|
|
Counterweight runby is 1", shorten cable to provide 6" of runby.
|
1/14/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
8.11.2.2.7
|
x
|
|
Elevators connected to a standby or emergency generator shall be tested for operation on standby or emergency power. Re-inspection required
|
1/21/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Category 5 full load test is incomplete. Need to perform the following tests: traction machine brake with 125% of rated load. Unintended car movement with 125% of rated load. Car safeties at rated speed with rated load. Car buffer at rated speed with rated load. Counterweight buffer at rated speed with no load. Re-inspection required
|
9/21/2024
|