Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 8.11.2.1.5(b) x Counterweight runby is 1", shorten cable to provide 6" of runby. 1/14/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.2.7 x Elevators connected to a standby or emergency generator shall be tested for operation on standby or emergency power. Re-inspection required 1/21/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Category 5 full load test is incomplete. Need to perform the following tests: traction machine brake with 125% of rated load. Unintended car movement with 125% of rated load. Car safeties at rated speed with rated load. Car buffer at rated speed with rated load. Counterweight buffer at rated speed with no load. Re-inspection required 9/21/2024