A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7
|
|
|
Upper demarcation lights not working
|
|
A17.1-1996 : Elevators
|
5.7 - Car frame and platform
|
203.6
|
|
|
Electric greenfield in bottom of controller torn open needs repair
|
|
A17.1-1996 : Escalators
|
7.5 - Lighting
|
805.7
|
|
|
Upper demarcation lights not working
|
|
A17.1-1996 : Escalators
|
7.5 - Lighting
|
806.2
|
|
|
Reinspection of demarcation lightening-failed and torn elect conduit on pit failed. No violations have been corrected. Reinspection needed
|
|
A17.1-1996 : Escalators
|
8.1 - Machinery space access, lighting, receptacle, and condition
|
806
|
|
|
Repair greenfield piping feeding the controller
|
|
Missouri Minimum : Escalators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) display of certificate
|
|
|
Post current state certificate in machine room
|
|
Missouri Minimum : Escalators
|
(T) - Existing Dumbwaiters, Escalators and Moving Walks
|
8.6.1.4 Maintenance Records
|
|
|
Need maintenance control program on site.
|
|
Missouri Minimum : Escalators
|
(T) - Existing Dumbwaiters, Escalators and Moving Walks
|
8.6.8.4 Escalator Combplates
|
x
|
|
Complete annual test top comb impact test, skirt switches etc.
|
|