A17.1-2016 : Elevators
|
5.15.2 Unsealed Overspeed Valve
|
8.6.5.16.5 (Re-Inspect)
|
x
|
|
Unsealed OSV - noted on last inspection report. Need to perform test of valve, seal and tag.
|
1/26/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
8.6.4.15 Emergency Lighting
|
x
|
|
The emergency car lighting is not operational.The fixture shall be repaired to operate. Reinspection required.
|
3/29/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.1 - Access to machine space
|
2.7.3.4
|
|
|
The elevator machine room door shall be self-closing, repair door closer.
|
3/29/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
There is no fire extinguisher in the machine room, as required. Provide an ABC type extinguisher of proper size for the room.
|
3/29/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.2.1 Phase 1 Emergency Recall OperationBy Fire Alarm initiating Devices
|
x
|
x
|
The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: Fire alarm initiating devices are off-line. The alarm panel shall be back in service and a reinspection performed before the elevator can be returned to service.
|
3/29/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not work.
|
5/7/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
Fire extinguisher needs to be serviced or replaced.
|
3/5/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
OSV is not sealed. Test valve on or before next annual inspection.
|
3/5/2021
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Not enough lighting in machine room, no less than 10 fc
|
|