Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone does not work. 5/7/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 Fire extinguisher needs to be serviced or replaced. 3/5/2021
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Not enough lighting in machine room, no less than 10 fc
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing OSV is not sealed. Test valve on or before next annual inspection. 3/5/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 2.7.3.4 The elevator machine room door shall be self-closing, repair door closer. 3/29/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Emergency Lighting x The emergency car lighting is not operational.The fixture shall be repaired to operate. Reinspection required. 3/29/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2.1 Phase 1 Emergency Recall OperationBy Fire Alarm initiating Devices x x The fireman's emergency service phase I and II operations was tested and the following deficiency was noted: Fire alarm initiating devices are off-line. The alarm panel shall be back in service and a reinspection performed before the elevator can be returned to service. 3/29/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 There is no fire extinguisher in the machine room, as required. Provide an ABC type extinguisher of proper size for the room. 3/29/2024
A17.1-2016 : Elevators 5.15.2 Unsealed Overspeed Valve 8.6.5.16.5 (Re-Inspect) x Unsealed OSV - noted on last inspection report. Need to perform test of valve, seal and tag. 1/26/2024