Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.11 - Plunger and Cylinder 3.18 The hydraulic cylinder gland packing is leaking excessively and shall be replaced. 3/13/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.11 - Plunger and Cylinder 8.6.5.5 Gland Packings and Seals The hydraulic cylinder gland packing is leaking excessively and shall be replaced. 6/11/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.11 - Plunger and Cylinder 8.6.5.5 Gland Packings and Seals x x Hydraulic jack cylinder head packing is leaking excessively. During the 15 minute standing test, the car dropped onto the spring buffers after 5 minutes. Elevator Red-tagged and removed from service. Re-inspection required 6/25/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.7 Record of Oil Usage Remove scavenger line connected to hydraulic jack that returns oil directly to hydraulic tank in elevator machine room. Oil usage shall be monitored. Remove scavenger line and place into 5 gallon bucket in elevator pit.