Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x reprogram the emergency phone, got error message that call could not be completed as dialed 4/24/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.17 - Drive machine brake 2.16.8 x 125% weight test was not completed 7/7/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.29 - Car and counterweight safeties 2.17 x x did not set the safeties with 100% load and measure the stopping distance 7/7/2020
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(c)(2) A record of findings for firefighters’ service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept in the machine room.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Post instructions for viewing on-site the records for the Maintenance Control Program (MCP)
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.21 - Governor releasing carrier 2.17.15 x x GOVENOR PULL THRU TESTING NOT DONE AT THIS TIME EQUIPMENT NOT AVALIABLE 3/14/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters Emergency Operation: Monthly Testing Post monthly fire service test log in the machine room
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters Emergency Operation: Monthly Testing a monthly fire service test log is to be kept in the machine room
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate a new copy of the state operating certificate is to be posted int the machine room every year
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current copy of the State Operating Certificate in the machine room