Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current operating certificate inside machine room.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.9 - Floor and emergency identification numbering 2.29.2 Number inside of hoistway doors for identification.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters Emergency Operation: Monthly Testing Test and log firefighter operation monthly
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Post emergency evacuation of passengers procedure in the machine room
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.7.2 Periodic Test Record (Test Tags) Install metal test tag for periodic pressure relief test
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state operating certificate inside the machine room
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.9 - Floor and emergency identification numbering 8.11.2.1.3(o) Identify the inside of hoistway doors with a numeral corresponding to the landing floor
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.36 - Hydraulic Cylinders 8.6.5.5.2 Collection of Oil Leakage Install cylinder drain line hose and pit collection container.
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) No maintenance control plan
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(a)(1) No maintenance records on site
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.7.2 Periodic Test Record (Test Tags) Attach metal test tag for documentation of periodic annual pressure relief test
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate State operating certificate not displayed in machine room
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.9 Elevator Corridor Call Station Pictograph Post In Case of Fire signage next to hall button fixture at each landing
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.11 - Disconnecting Means and Control 2.26.4 Machine room mainline breaker disconnect is not lockable in the open position
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.11 - Disconnecting Means and Control 2.26.4 Machine room 110 volt cab lighting breaker disconnect is not lockable in the open position
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.36 - Hydraulic Cylinders 8.6.5.5.2 Collection of Oil Leakage Install cylinder drain line and pit collection container
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate State operating certificate not displayed
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.11 - Disconnecting Means and Control 2.26.4 Main line disconnect not capable of being locked in the open position.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.11 - Disconnecting Means and Control 2.26.4 110VAC car light disconnect not capable of being locked in the open position.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters Emergency Operation: Monthly Testing Test and log firefighter operation monthly.
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) Post emergency evacuation of passengers form inside machine room.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.1.1(q) x Emergency return unit does not supply auxillary power. 1/21/2019
conversion conversion n/a Emergency light and bell do not operate 1/15/2020
A17.1-2016 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Car Emergency System (Re-Inspection) x Emergency light does not operate. 1/27/2021