ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.11 - Disconnecting Means and Control 2.26.4 No No 110VAC car light disconnect not capable of being locked in the open position. 8/10/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.7.2 Periodic Test Record (Test Tags) No No Attach metal test tag for documentation of periodic annual pressure relief test 8/10/2026
A17.1-2016 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Car Emergency System (Re-Inspection) Yes No Emergency light does not operate. 1/27/2021
conversion conversion n/a No No Emergency light and bell do not operate 1/15/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.1.1(q) Yes No Emergency return unit does not supply auxillary power. 1/21/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.9 - Floor and emergency identification numbering 8.11.2.1.3(o) No No Identify the inside of hoistway doors with a numeral corresponding to the landing floor 8/10/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.36 - Hydraulic Cylinders 8.6.5.5.2 Collection of Oil Leakage No No Install cylinder drain line and pit collection container 8/10/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.36 - Hydraulic Cylinders 8.6.5.5.2 Collection of Oil Leakage No No Install cylinder drain line hose and pit collection container. 8/10/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.7.2 Periodic Test Record (Test Tags) No No Install metal test tag for periodic pressure relief test 8/10/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.11 - Disconnecting Means and Control 2.26.4 No No Machine room 110 volt cab lighting breaker disconnect is not lockable in the open position 8/10/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.11 - Disconnecting Means and Control 2.26.4 No No Machine room mainline breaker disconnect is not lockable in the open position 8/10/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.11 - Disconnecting Means and Control 2.26.4 No No Main line disconnect not capable of being locked in the open position. 8/10/2026
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) No No No maintenance control plan 8/10/2026
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.4.1(a)(1) No No No maintenance records on site 8/10/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.9 - Floor and emergency identification numbering 2.29.2 No No Number inside of hoistway doors for identification. 8/10/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current operating certificate inside machine room. 8/10/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current state operating certificate inside the machine room 8/10/2026
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(a) No No Post emergency evacuation of passengers form inside machine room. 8/10/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No Post emergency evacuation of passengers procedure in the machine room 8/10/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.9 Elevator Corridor Call Station Pictograph No No Post In Case of Fire signage next to hall button fixture at each landing 8/10/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No State operating certificate not displayed 8/10/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No State operating certificate not displayed in machine room 8/10/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters Emergency Operation: Monthly Testing No No Test and log firefighter operation monthly 8/10/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters Emergency Operation: Monthly Testing No No Test and log firefighter operation monthly. 8/10/2026