ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.14 - Ventilation
|
2.14.2.3
|
|
|
Cab ventilation fan shall work with and without 120v. (Battery backup for Glassback/Observation)
|
10/29/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
t State Operating Permit shall be displayed in the Equipment Room in a non-combustible frame.
|
10/29/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.3 - Operating control devices
|
8.11.2.1.1(c)
|
|
|
1.3: Car Position Indicator shall work.
|
10/29/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
2-way communication device shall work and give proper location (REINSPECTION within 30 days
|
10/29/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.23 - Suspension rope
|
8.11.2.1.3(cc)
|
|
|
3.23 : Hoist Ropes appear dry and showing “rouge”. Ropes shall be cleaned and lubricated per OEM recommendations
|
10/29/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
MCP shall be kept in equipment room, including Testing Procedure(not present) and Fire service testing log, recorded monthly.
|
10/29/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.17 - Door and gate equipment
|
8.6.4.13 Door Systems
|
x
|
|
Hoistway/Car door gib fire tabs shall be engaged into the guideway(sill). (3rd floor)
|
10/29/2020
|