Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.1.6(h) Phase 2 Audible/Visual Signal (Re-Inspection) Phase 1 Fire Hat does not work 6/2/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate needs current certificate posted 10/1/2020
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Repair Phase 1 switch, spins but works. REINSPECTION REQUIRED 6/2/2022
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Repair Phase 1 switch, spins but works. REINSPECTION REQUIRED 6/2/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x 2-way communication device shall work and give proper location. Agent could not hear conversation intermittently (as if microphone had issues) 3/1/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.6.4.8 Machine Rooms and Machinery Spaces 8.6.4.8.2 Material or articales not for elevator shall not be stored in machine room 10/1/2020