Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Repair emergency phone and alarm bell. 7/24/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.1 No No Repair non-functioning 120 volt receptacle in elevator machine room. 4/23/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No The emergency alarm shall work. 2/27/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Yes No Bad roller top counterweight. Take corrective action as needed. 2/27/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Yes No There is a broken bracket on the brake arm. Take corrective action as needed. 2/27/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.11.2.2.6 Fire Fighters Operation (Re-Inspection) Yes No There are no smoke or heat detectors present except 1 smoke detector in the machine room. The device is the machine room is not tied into the elevator. Based on the installation year of 2009, fire alarm initiating devices shall be provided to initiate Phase 1 Emergency recall operation and shall be installed in conformance with the requirements of NFPA 72. 2/27/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Emergency Lighting Yes No The emergency light shall work. 2/27/2025