Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts x 4 Counterweight rollers on top are no good. The parts are ordered - leaving elevator down until replaced.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency alarm shall work.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.11.2.2.6 Fire Fighters Operation (Re-Inspection) x There are no smoke or heat detectors present except 1 smoke detector in the machine room. The device is the machine room is not tied into the elevator. Based on the installation year of 2009, fire alarm initiating devices shall be provided to initiate Phase 1 Emergency recall operation and shall be installed in conformance with the requirements of NFPA 72.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Emergency Lighting x Emergency light shall work.
conversion conversion conversion - reinspect x Repair emergency phone and alarm bell. 7/24/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.1 Repair non-functioning 120 volt receptacle in elevator machine room. 4/23/2020