Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.1.1(q) x Emergency Power is existing but was not tested. 3/7/2020
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.4.19.6 x Unable to test Firefighters' Service - schedule test. 2/16/2021
A17.1-2016 : Elevators 3.23 - Suspension Means 8.11.2.1.3(cc) x Suspension ropes undersized per A17.6. 1/20/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.4 - Machine space 2.7.1.1 Hole in machine room wall boarded up with plywood, not fire-rated. 9/8/2023