Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.1.6(h) Phase 2 Audible/Visual Signal (Re-Inspection) x In-car visual FS signal not flashing when machine room initiating devices (smokes) activated. 1/20/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.12 - Standby power selection switch 2.27.2 Emergency power visual indicator (jewel) in fire command room not working. 9/11/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.12 - Standby power selection switch 2.27.2 Emergency power visual indicator (jewel) in hall station not working. 9/11/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.4 - Machine space 2.7.1.1 Hole in machine room wall boarded up with plywood, not fire-rated. 9/8/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.4 - Machine space 2.7.1.1 Machine room enclosure must maintain fire rating. Voids in wall during building vertical expansion construction.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Two way communication does not work on emergency/battery. Also operator says it needs to show Institute of Health on her screen 1/28/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.1.1(q) x Emergency Power is existing but was not tested. 3/7/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2.3 (Elevator Emergency Power Illuminated Signal) Emergency power indicator in hall not lighting.