Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) No No Unique procedures or methods for tests and inspections not described in A17.2 shall be kept in the elevator machine room.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Incomplete test, unintended motion, and fire service shall be tested 1/14/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Test is incomplete, need to perform unintended car movement test. Re-inspection required 7/24/2025
A17.1-2016 : Elevators 2.17 - Drive machine brake 8.6.4.19.11 Ascending Overspeed Protection, Unintended Movement Devices, and Emg Brake Yes No The rope gripping device that is installed on this unit to conform for unintentional movement of the elevator car is activating whenever the hoistway door is accessed. Per A17.1 20004a 2.19.2.2, to which this elevator is installed to, opening of the hoistway door is not one of the devices to which the rope gripper shall activate. The device shall be repaired and a reinspection is required. 12/12/2022
A17.1-2016 : Elevators 2.42 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater) 8.6.4.19.17 Earthquake Operation Yes No Seismic displacement device on counterweights does not work, needs repaired. Re-inspection required