Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (I) - Pits (I)1 oil on pit floor 4/26/2024
MO Minimum : Elevators (I) - Pits (I)1 oil on pit floor 4/26/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2.3 (Elevator Emergency Power Illuminated Signal) emg power illumination lt not working 4/26/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2.3 (Elevator Emergency Power Illuminated Signal) illumination lt didnt work
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x phone wasnt answeredin the allotted time an when it was thy couldt idenify the proper elev.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency Telephone not functioning. No outside line must Reinspect. 12/9/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x Emergency Power Operation and Transfer Switch could not ne witnessed on the day selected for the annual inspection. Must re-schedule test. 12/9/2024
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x unable to test emg. power at time of insp. 10/2/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.1.1(q) x All elevators on EP Generator. Could not test Power Transfer due to surgery schedules. Must Re-reschedule EP Transfer test. 7/28/2021
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Standby power not tested 3/7/2022