MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
oil on pit floor
|
4/26/2024
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
oil on pit floor
|
4/26/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency Telephone not functioning. No outside line must Reinspect.
|
12/9/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
Emergency Power Operation and Transfer Switch could not ne witnessed on the day selected for the annual inspection. Must re-schedule test.
|
12/9/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
2.27.2.3 (Elevator Emergency Power Illuminated Signal)
|
|
|
illumination lt didnt work
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
2.27.2.3 (Elevator Emergency Power Illuminated Signal)
|
|
|
emg power illumination lt not working
|
4/26/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
8.11.2.1.1(q)
|
x
|
|
All elevators on EP Generator. Could not test Power Transfer due to surgery schedules. Must Re-reschedule EP Transfer test.
|
7/28/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
phone wasnt answeredin the allotted time an when it was thy couldt idenify the proper elev.
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Standby power not tested
|
3/7/2022
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
unable to test emg. power at time of insp.
|
10/2/2023
|