ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators
|
7.3 - Handrails
|
8.6.8.1
|
|
|
Right side handrail is dry rotting and cracking in multiple places creating pinching hazards. Replace hand rail
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators
|
7.4 - Entrance and egress ends
|
6.1.3.12
|
|
|
Multi section landing plates are warped (top and bottom) and not level, causing a tripping hazard. Repair
|
10/8/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators
|
7.4 - Entrance and egress ends
|
6.1.3.12
|
|
|
Walking surface adjacent to top landing plate is not level with landing plate causing a tripping hazard. Repair
|
10/8/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators
|
8.3 - Controller and wiring
|
6.1.7
|
x
|
|
Controller inspection operation does not work.
|
10/8/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators
|
7.7 - Combplate and comb step impact device
|
6.1.8.3
|
x
|
|
Comb plate impact device is not moving freely. Test for tripping pressure.
|
10/8/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators
|
7.9 - Steps and upthrust device
|
6.1.3.5
|
x
|
|
Replace broken demarcation strip.
|
10/8/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators
|
7.4 - Entrance and egress ends
|
8.6.8.13
|
|
|
Repair trip hazard on top floor plate.
|
10/9/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators
|
8.12 - Steps, step chains, and trusses
|
8.11.4.2.12
|
|
|
Step chains are worn. Steps are 1/4" out of square with comb plates. Replace step chains.
|
9/11/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators
|
7.11 - Skirt obstruction device
|
6.1.6.3.6
|
x
|
|
Bottom skirt switches do not work.
|
9/11/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators
|
8.1 - Machinery space access, lighting, receptacle, and condition
|
8.6.8.15
|
|
|
Clean truss space and pits.
|
11/3/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators
|
7.5 - Lighting
|
6.1.6.7
|
|
|
Replace broken step demarcation strips.
|
11/3/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators
|
8.13 - Handrail systems and safety devices
|
8.11.4.2.13
|
|
|
Right side handrail drive belt missing.
|
11/3/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators
|
8.1 - Machinery space access, lighting, receptacle, and condition
|
8.6.8.13
|
|
|
Clean trusses and pit.
|
8/16/2021
|
Missouri Minimum : Escalators
|
(T) - Existing Dumbwaiters, Escalators and Moving Walks
|
8.6.8.14 Escalator Entrance and Egress Ends
|
|
|
Bottom walk plate loose, tripping hazard. Re-inspection required
|
12/7/2022
|
Missouri Minimum : Escalators
|
(T) - Existing Dumbwaiters, Escalators and Moving Walks
|
8.6.8.13 Escalator Cleaning
|
|
|
Need to clean truss & pits
|
12/7/2022
|