Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 7.11 - Skirt obstruction device 6.1.6.3.6 x Bottom skirt switches do not work. 9/11/2020
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.14 Escalator Entrance and Egress Ends Bottom walk plate loose, tripping hazard. Re-inspection required 12/7/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 8.1 - Machinery space access, lighting, receptacle, and condition 8.6.8.15 Clean truss space and pits. 11/3/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 8.1 - Machinery space access, lighting, receptacle, and condition 8.6.8.13 Clean trusses and pit. 8/16/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 7.7 - Combplate and comb step impact device 6.1.8.3 x Comb plate impact device is not moving freely. Test for tripping pressure. 10/8/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 8.3 - Controller and wiring 6.1.7 x Controller inspection operation does not work. 10/8/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 7.4 - Entrance and egress ends 6.1.3.12 Multi section landing plates are warped (top and bottom) and not level, causing a tripping hazard. Repair 10/8/2019
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.13 Escalator Cleaning Need to clean truss & pits 12/7/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 7.4 - Entrance and egress ends 8.6.8.13 Repair trip hazard on top floor plate. 10/9/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 7.9 - Steps and upthrust device 6.1.3.5 x Replace broken demarcation strip. 10/8/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 7.5 - Lighting 6.1.6.7 Replace broken step demarcation strips. 11/3/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 8.13 - Handrail systems and safety devices 8.11.4.2.13 Right side handrail drive belt missing. 11/3/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 7.3 - Handrails 8.6.8.1 Right side handrail is dry rotting and cracking in multiple places creating pinching hazards. Replace hand rail
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 8.12 - Steps, step chains, and trusses 8.11.4.2.12 Step chains are worn. Steps are 1/4" out of square with comb plates. Replace step chains. 9/11/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 7.4 - Entrance and egress ends 6.1.3.12 Walking surface adjacent to top landing plate is not level with landing plate causing a tripping hazard. Repair 10/8/2019