Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
Missouri Minimum : Escalators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Need to perform testing of handrail speed sensors, demarcation lights, and missing step sensors and comb impact switches to complete the inspection. Re-inspection required
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Annual inspection is incomplete. Must do top comb impact and step indexing to complete the annual inspection 3/15/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 7.4 - Entrance and egress ends 6.1.3.12 Walking surface adjacent to top landing plate is not level with landing plate causing a tripping hazard. Repair 10/9/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 7.4 - Entrance and egress ends 6.1.3.6 Multi section landing plates are warped and (top and bottom) not level causing a tripping hazard. Repair 10/9/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 7.7 - Combplate and comb step impact device 6.1.6.3.13 x Comb plate impact device is not moving freely. Test for tripping pressure. 10/9/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 7.3 - Handrails 8.11.4.1 (c) Replace both handrails. 10/9/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 7.3 - Handrails 8.11.4.2.13 Replace both handrails. 8/16/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 7.9 - Steps and upthrust device 8.11.4.2.9 x Replace broken demarcation strips. 10/9/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Need to replace broken run keyswitch at bottom end
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts x x Step chains are worn and need to be replaced. Red-tagged, Re-inspection required
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.1 Escalator Handrails Right handrail is cracked, replace same
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.1 Escalator Handrails x Replace both hand rails. Re-inspection required 9/15/2022
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.1 Escalator Handrails Handrails still need to be replaced 12/7/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 7.4 - Entrance and egress ends 8.6.8.13 Repair loose floor tile at top floor plate. 10/9/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 7.4 - Entrance and egress ends 8.6.8.13 Bottom walk on plate is separating creating a trip hazard. 8/16/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 8.1 - Machinery space access, lighting, receptacle, and condition 8.6.8.13 Clean truss spaces and pit. 8/16/2021
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.13 Escalator Cleaning Need to perform clean down of unit
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.13 Escalator Cleaning Truss space still needs to be cleaned 12/7/2022
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.13 Escalator Cleaning Need to clean truss spaces & pits. Red tagged, Re-inspection required 12/7/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Escalators 8.1 - Machinery space access, lighting, receptacle, and condition 8.6.8.14 Clean truss space and pits. 11/3/2020
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.14 Escalator Entrance and Egress Ends x x Bottom walk on plate is separating, creating tripping hazard. Red tagged, Re-inspection required 9/15/2022
Missouri Minimum : Escalators (T) - Existing Dumbwaiters, Escalators and Moving Walks 8.6.8.2 Escalator Step-to-Skirt Clearance x Unit failed skirt indexing test. Correct gap and retest. Re-inspection required