Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) No No need to have written procedures on how to perform annual tests and 5 year tests 5/27/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.10 - Numbering of elevators, machines, and disconnect switches 8.11.2.1.2(j) No No The hoistway side of the hall doors need to be numbered 5/27/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Repair/replace the car top inspection station, the inspecion switch is broken off and missing. can not put car on inspection at the car top inspection station 5/27/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No one of the two emergency lights did not work 10/4/2022
A17.1-2016 : Elevators 2.36 - Hydraulic Cylinders 8.6.5.8 Yes No Replace single bottom cylinder. Car safeties installed years ago. No variance on record and building owner could not provide documentation of a variance. 9/8/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No Replace broken top of car inspection switch. 9/8/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates No No Post In Case of Fire signage next to hall button fixture at each landing 9/8/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates No No Number hoistway side of hall doors 9/8/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No No maintenance records in machine room 9/8/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation No No No maintenance control plan in machine room 9/8/2026
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11.3.2.2 Cylinders Test shall be performed Yes No Perform cylinder test 9/8/2026
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No State operating certificate not displayed in machine room 9/8/2026
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)2(D) Yes No Need to seal relief valve on hydraulic machine 9/8/2026
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Machine room access door shall be self-closing and self-locking 9/8/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No Emergency light has a defective lamp 9/8/2026
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)7 Yes No Door force exceeds 30 # 9/8/2026
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Perform pressure relief test 9/8/2026