ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.10 - Numbering of elevators, machines, and disconnect switches
|
8.11.2.1.2(j)
|
|
|
The hoistway side of the hall doors need to be numbered
|
5/27/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests)
|
|
|
need to have written procedures on how to perform annual tests and 5 year tests
|
5/27/2021
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Machine room access door shall be self-closing and self-locking
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
Post In Case of Fire signage next to hall button fixture at each landing
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
Number hoistway side of hall doors
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
Replace broken top of car inspection switch.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.2.1 General Maintenance Requirements Documentation
|
|
|
No maintenance control plan in machine room
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
No maintenance records in machine room
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
State operating certificate not displayed in machine room
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
Repair/replace the car top inspection station, the inspecion switch is broken off and missing. can not put car on inspection at the car top inspection station
|
5/27/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
one of the two emergency lights did not work
|
10/4/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Perform pressure relief test
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.11.3.2.2 Cylinders Test shall be performed
|
x
|
|
Perform cylinder test
|
|
MO Minimum : Elevators
|
(O) - Existing Hydraulic Elevators
|
(O)2(D)
|
x
|
|
Need to seal relief valve on hydraulic machine
|
|
A17.1-2016 : Elevators
|
2.36 - Hydraulic Cylinders
|
8.6.5.8
|
x
|
|
Replace single bottom cylinder. Car safeties installed years ago. No variance on record and building owner could not provide documentation of a variance.
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)7
|
x
|
|
Door force exceeds 30 #
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
Emergency light has a defective lamp
|
|