MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.11.1.4(a) Elevators Placed in Inactive Status
|
x
|
x
|
elev cab an controller flooded cust. waiting for repair an replacement bid
|
5/5/2023
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.10.2.2.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
x
|
Install phone inside elevator to provide means for emergency communication. A17.1 5.7.21
|
7/21/2023
|
A17.1-2016 : Elevators
|
3.12 - Pipes, wiring, and ducts
|
8.10.2.2.3(r)
|
x
|
x
|
Electrical cables exiting traveling cable junction box and routed on the outer side wall and back wall of the elevator need to be in conduit. The cables are rated FT-2 and exceed 6 ft in length. Elevator is in a coal dust environment. A17.1 2.8
|
7/21/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
4.8 - Hoistway enclosure
|
8.11.2.1.4(h)
|
x
|
|
Reinforce hoistway enclosure at top landing to maintain strength of the enclosure. Bracing of the enclosure to building support needs to be repaired. A17.1. 5.7.1.1
|
7/21/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
x
|
|
Elevator pit has approx 6 inches of water. Provide means to prevent accumulation of water in the pit. Pit shall be kept dry.
|
7/21/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.17 - Drive machine brake
|
2.24.8.4 Means for Manual Release
|
x
|
|
Manual emergency brake release shall reapply the brake at fully adjusted capacity in the absence of hand applied effort.
|
7/21/2023
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
provide working phone (no dial tone)
|
6/14/2024
|