Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.10.2.2.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x x Install phone inside elevator to provide means for emergency communication. A17.1 5.7.21 7/21/2023
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 8.10.2.2.3(r) x x Electrical cables exiting traveling cable junction box and routed on the outer side wall and back wall of the elevator need to be in conduit. The cables are rated FT-2 and exceed 6 ft in length. Elevator is in a coal dust environment. A17.1 2.8 7/21/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.8 - Hoistway enclosure 8.11.2.1.4(h) x Reinforce hoistway enclosure at top landing to maintain strength of the enclosure. Bracing of the enclosure to building support needs to be repaired. A17.1. 5.7.1.1 7/21/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits x Elevator pit has approx 6 inches of water. Provide means to prevent accumulation of water in the pit. Pit shall be kept dry. 7/21/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.17 - Drive machine brake 2.24.8.4 Means for Manual Release x Manual emergency brake release shall reapply the brake at fully adjusted capacity in the absence of hand applied effort. 7/21/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x provide working phone (no dial tone) 6/14/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.11.1.4(a) Elevators Placed in Inactive Status x x elev cab an controller flooded cust. waiting for repair an replacement bid 5/5/2023