Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Need to perform the following tests to complete Cat 5 full load test: test driving machine brake with 125% of rated load, perform unintended movement test with 125% of rated load, test car safeties with rated load at rated speed, test car buffer with rated load at rated speed & test counterweight buffer at rated speed. Re-inspection required
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.8 Switch Keys (Re-Inspection) x All fire service keys for elevators in one building shall be keyed alike 12/6/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.11.2.2.6 x All fire service keys for elevators in one building shall be keyed alike. Re-inspection required 3/13/2023