ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.8 Switch Keys (Re-Inspection)
|
x
|
|
All fire service keys for elevators in one building shall be keyed alike
|
12/6/2022
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.11.2.2.6
|
x
|
|
All fire service keys for elevators in one building shall be keyed alike. Re-inspection required
|
3/13/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Need to perform the following tests to complete Cat 5 full load test: test driving machine brake with 125% of rated load, perform unintended movement test with 125% of rated load, test car safeties with rated load at rated speed, test car buffer with rated load at rated speed & test counterweight buffer at rated speed. Re-inspection required
|
|