Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x Battery lowering shall work. Repair or replace. 9/20/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x Battery lowering shall work. Repair or replace. Multi-year violation. Unit not red tagged due to other 2 units at location being red tagged. Owner/management has 15 days from date of inspection to get both violations corrected or this unit will be red tagged as well.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.17 - Drive machine brake 2.24.8.3 x Repair/replace emergency brake release. Multi-year violation. Unit not red tagged due to other 2 units at location being red tagged. Owner/management has 15 days from date of inspection to get both violations corrected or this unit will be red tagged as well.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.17 - Drive machine brake 2.24.8.4 Means for Manual Release x Repair/replace emergency brake release. 9/20/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 MCP including PM records and monthly fire service test log, not being properly documented.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state certificate in machine room 9/22/2023